The following parameters must be set as below:
Drive
|
Connection Type
|
Parameter
|
Description
|
Recommended
|
SSW-06
|
RS232
|
308
|
SSW Address
|
1
|
309
|
Fieldbus
|
0: Inactive
|
312
|
Serial Protocol
|
1: MB 9600 N
(Modbus-RTU 9600 bps, no parity)
|
SSW-07
|
RS232
|
308
|
SSW Address
|
1
|
312
|
Serial Protocol
|
1: MB 9600 N
(Modbus-RTU 9600 bps, no parity)
|
CFW-09 PM
|
RS232
|
308
|
Serial:Address
|
1
|
310
|
Serial:Bit Rate
|
1: 9600 bps
|
311
|
Serial:Data Con.
|
3: 8b,no p,2sb
|
312
|
Serial:Protocol
|
2: Modbus-RTU
|
CFW-11
|
USB
|
-----
|
-----
|
-----
|

|
Drive and SuperDrive G2 must use the same settings.
|
|
For SSW, P308 and P312 can be changed, see Serial Communication Manual.
|
|
For CFW-09 PM, P308, P310 and P311 can be changed, see Frequency Inverter Manual - CFW-09 PM.
|
|